PAT Testing: 15 Things the HSE Actually Says About Intervals

A
Arinite Health & Safety Consultants
November 16, 2026
11 min read
PAT Testing: 15 Things the HSE Actually Says About Intervals

Every year a contractor arrives at an office, works through the building with a tester, puts a green sticker on several hundred items and issues a certificate. Facilities files it, finance pays it, and everybody assumes that is what the law requires.

It is not. The Health and Safety Executive's guidance for low-risk workplaces says that not every electrical item needs a portable appliance test, that equipment which does need one may not need it every year, and that there is no legal requirement to label equipment or keep records of the tests.

On the HSE's own suggested intervals, a double insulated desktop computer needs no user check and no test at all. It needs a formal visual inspection every two to four years. A battery-operated item and a telephone need nothing.

That matters commercially, because many organisations pay annually for something the guidance suggests should happen every few years, while the item that fails most often, the extension lead under a desk, is grouped in with everything else. Here are fifteen things the guidance says, drawn from INDG236 and the HSE's electrical safety pages.

What the law requires

1. The duty is to maintain, not to test. Regulation 4(2) of the Electricity at Work Regulations 1989 says that as may be necessary to prevent danger, all systems shall be maintained so as to prevent, so far as is reasonably practicable, such danger.

That is the whole of it. The word test does not appear, and neither does any interval. Our note on the Electricity at Work Regulations covers the wider duties.

2. The HSE says the law does not specify how or how often. Its guidance puts it plainly: you must maintain electrical equipment if it can cause danger, but the law does not say how you must do this or how often. You decide the level of maintenance according to the risk of an item becoming faulty and how the equipment is constructed.

3. Two risk factors are named. You should consider the increased risk if equipment is not used correctly, is not suitable for the job or is used in a harsh environment, and whether the item is double insulated or earthed.

4. Not every item needs a test. Stated in terms: in some cases a simple user check and visual inspection is enough. Other equipment, such as a floor cleaner or kettle, may need a test, but not necessarily every year.

5. There is no duty to label or to keep records. The guidance says you may find it useful to keep records of inspections and tests, and to label equipment with the result and date, but there is no legal requirement to do either.

Worth knowing before the next renewal quote. Records are often genuinely useful as evidence, which is a different argument from a legal obligation, and it is the argument to make rather than the one usually made.

The three levels of check

6. User checks, before use, with the equipment disconnected. The first level, and free. Employees look for damage to the lead including fraying, cuts or heavy scuffing, damage to the plug, tape joining leads, coloured wires visible where the lead meets the plug, damage to the equipment casing including loose parts or screws, signs of overheating such as burn marks or staining, equipment used or stored in unsuitable conditions, and cables trapped under furniture or in floor boxes.

7. Formal visual inspection does not need an electrician. The guidance is explicit: you do not need to be an electrician, but you do need to know what to look for and to have sufficient knowledge to avoid danger. Simple training can equip a member of staff to do it competently.

This is the finding that changes the cost picture in most offices. The level of check the HSE suggests for the bulk of office equipment can be done in-house by a trained member of staff.

8. What the visual inspection adds. Beyond the user checks, it asks whether the equipment is used in accordance with the manufacturer's instructions, whether it is suitable for the job, whether circumstances have changed, and whether the user has reported anything. Where possible it includes removing the plug cover to check for internal damage, the correct fuse rather than a piece of wire, wires on the correct terminals, tight terminal screws, a cord grip holding the cable sheath, and no bare wire outside the terminals. On moulded plugs only the fuse can be checked. The fuller technical guidance sits in HSG107.

9. The test itself does not need an electrician either, but it needs more. A portable appliance test does not have to be carried out by an electrician, but greater knowledge and experience is needed than for inspection alone, the person must have the right equipment, and they must know how to use it and how to interpret the results.

Equipment class decides most of it

10. Class II double insulated equipment will not need a test. The guidance states that Class II equipment does not need an earth connection to maintain safety and will not need a portable appliance test, although user checks and visual inspections should still be carried out because the integrity of the casing is a key safety feature.

11. If you cannot see the Class II symbol, assume Class I and test. A simple and useful default, and the one practical reason to look at the back of an item before deciding.

12. Battery and extra low voltage equipment need nothing. On the HSE's table, battery-operated equipment below 40 volts and extra low voltage equipment below 50 volts AC, which it exemplifies as telephone equipment and low-voltage desk lights, require no user check, no visual inspection and no testing.

13. Leads and extension leads are the real population. Cables, leads and plugs connected to equipment, along with mains voltage extension leads and battery-charging equipment, carry user checks, formal visual inspection every six months to four years, and testing every one to five years, depending on the equipment they are connected to.

In an office this is where the damage actually is, and it is the category most often treated as an afterthought behind the computers.

Intervals, and how to set them

14. Group by interval, and use the shortest in any group. A note under the HSE's table that nobody follows: if electrical equipment is grouped together for testing at the same time, you should use the shortest testing interval in the group rather than the longest. Alternatively, group your equipment by testing interval.

A single annual visit across an entire building is the opposite of this, and it is both more expensive and less targeted than the guidance suggests.

15. Review the intervals against what you find. You should review the maintenance system to decide whether to decrease or increase inspection and testing intervals, and the guidance notes that over time the results of checks, inspections and tests will show trends which may tell you to look at equipment less or more often.

So the correct output of a programme is a revised interval, not a renewed contract at the same frequency.

The HSE's suggested initial intervals

Equipment or environmentUser checksFormal visual inspectionCombined inspection and testing
Battery-operated, under 40 voltsNoNoNo
Extra low voltage, under 50 volts AC: telephones, low-voltage desk lightsNoNoNo
Desktop computers, VDU screensNoYes, 2 to 4 yearsNo if double insulated, otherwise up to 5 years
Photocopiers, fax machines, not hand-held, rarely movedNoYes, 2 to 4 yearsNo if double insulated, otherwise up to 5 years
Class II, not hand-held, moved occasionally: fans, table lampsNoYes, 2 to 4 yearsNo
Class II, hand-held: some floor cleaners, some kitchen equipmentYesYes, 6 months to 1 yearNo
Class I earthed: kettles, some floor cleaners, some kitchen equipment, ironsYesYes, 6 months to 1 yearYes, 1 to 2 years
Cables, leads, plugs, extension leads, battery chargersYesYes, 6 months to 4 yearsYes, 1 to 5 years

Read the third row against the invoice. Desktop computers and screens are the largest population in any office, and on the HSE's own table they need a visual inspection every two to four years and, if double insulated, no test at all.

Two notes the HSE attaches. Cables and leads dedicated to a Class II item are maintained as part of that item, while leads not dedicated to anything are maintained individually. And these are initial intervals, to be adjusted by what you find.

Holding an asset register with the class, the interval and the date of the last check against each item is a practical case for health and safety consultants and software working as one system, because the whole point is that different items are on different cycles. Periodic health and safety audits should ask the question that exposes the problem: what interval are we on, and who decided it.

Who owns the equipment you do not own

The part contracts miss. The guidance says the duty covers any electrical equipment your employees use at work, whether it is their own or supplied by you. For leased equipment such as a photocopier, or equipment provided by a contractor, you have a joint responsibility. The exception is equipment both provided and used by a contractor, which is theirs.

Three consequences. Home and hybrid workers using their own chargers and leads are inside the duty, which our note on hot desking and hybrid teams touches on. Leased equipment is a shared duty, not the lessor's problem. And the cleaner's vacuum, if the cleaning company brings and uses it, is not yours. Our notes on contractors in your office and outsourced facilities management cover the boundary, comms rooms the server question, and the fit out brief what to specify for new equipment.

How this travels internationally

For groups with offices in several countries, portable equipment maintenance is a good example of a British regime that is risk-based where others are prescriptive.

The British position sets an outcome, maintain so as to prevent danger so far as is reasonably practicable, and leaves method and interval to the employer, with guidance offering starting points. There is no mandated test, label or record.

Several other jurisdictions do the reverse: periodic inspection at intervals fixed in regulation rather than by assessment, carried out or certified by an approved body rather than a competent person of the employer's choosing, with a certificate in a national format. Germany is the clearest example among the regimes we work in, and our note on DGUV and equipment inspection covers it.

So the asset register and the class of each item export. The interval, the certifying party and the record format do not, and a group standard built on the British table will understate what several countries require while over-testing here.

Where Arinite fits

Arinite does not carry out portable appliance testing and has nothing to sell you on a two-year cycle. What our health and safety consultants do is establish what equipment you actually have, what class it is, which items the guidance says need nothing, and what interval is defensible for the rest. In our experience that conversation usually reduces the testing bill and moves attention to leads and hand-held items, which is where the faults are. We support 1,500+ businesses in 50+ countries and protect 100,000+ employees, with 95%+ client retention over 15+ years.

We work extensively with office-based, legal, insurance, IT and software, education and property and real estate clients, which is precisely the low-risk environment the HSE's guidance was written for. Our note on whether PAT testing is a legal requirement answers the question directly, and this duty belongs with the recurring set in our note on statutory building checks.

For multi-country groups, our global health and safety consultants apply the local interval and certifying body rather than exporting a British risk-based approach, and our international health and safety consultants can tell you which sites have intervals fixed by regulation.

Do one thing before the next renewal. Ask what interval your programme runs on, who set it, and how many of the items on the last certificate were double insulated computers and monitors. Then book a free gap analysis and we will tell you in one call whether you are testing the right things at the right frequency.

Share this article
A

Written by

Arinite Health & Safety Consultants

Health & Safety Expert at Arinite

Free Resources

Health & Safety Factsheets

Download our comprehensive library of expert guides, checklists, and templates.

Get Professional Help

Need Expert H&S Advice?

Our qualified consultants are ready to support your specific business needs.